LOCATIONS EBUSINESS CAREERS

100 to 2,000 kVA

The G9000 Series UPS comes with an industry-leading three-year onsite warranty. It is designed for stand-alone or parallel use in up to eight-unit configurations without requiring the use of a special switchgear cabinet.

Using the new Toshiba IGBT technology in the rectifier/converter, DC/DC chopper, and the inverter sections of the UPS, the G9000's double-conversion topology provides an AC/DC/AC efficiencies of up to 97% at loads from 50% to 100%. Even at 20% loading, the efficiency remains greater than 94%. This is 10% to 20% better than current industry systems, making the G9000 excellent for N+1 parallel systems where loads are typically 30-40%

Request a Quote

(100kVA to 1000kVA)

Toshiba G9000 UPS for data centres
Need Help? Call 416-639-1730

Features

  • Parallel upto 8 units (load capacity of 8 MVA)
  • Single or Dual Source Input
  • Input power factor > 0.99
  • Input Current THD < 3%
  • 100% Unbalanced load capacity
  • Wide input voltage range +15%, -20% (without using batteries)
  • Complete front-access for installation, operation and maintenance
  • Generator-friendly design and compatability
  • IGBT DC converter/inverter design
  • Generator-friendly design and compatability
  • SNMP/Web-Based monitoring
  • Handles leading ower factor loads (without derating)

A High Efficiency Design separates the G9000 from the competition. Efficiency greater than 92.5% at 20% loading means lower power losses, reduced air conditioning needs, and reduced utility costs across a wide load range without sacrificing frequency or output voltage stability.
High efficiency UPS at 20% load

Specs (100 kVA to 225 kVA)

Size 100 kVA
(90 kW)
160 kVA
(144 kW)
225 kVA
(202.5 kW)
Model Number
T90S3S10KS6XSN
**T90S3S10KS6XSN2**
T90S3S16KS6XSN
**T90S3S16KS6XSN2**
T90S3S22KS6XSN
**T90S3S22KS6XSN2**
Input Voltage  480 V, Three-Phase, Three-Wire + Ground/Bypass Input; 480 V, Three-Phase, Three-Wire + Ground
480V, -20% to +15% (383 to 552 V without using battery)
Input Power Factor >0.99
Current THD < 3% at 100% Load (No input filter required)
Input Frequency 60Hz +/-10%
Output Voltage 480 V, Three-Phase, Three-Wire + Ground
Output Frequency 60Hz, +/-0.01% (In free running mode)
Output Power Factor 0.9 Lagging
Overload Capacity Inverter: 125% for 2 min; 150% for 60 sec
Bypass: 1000% for one cycle
 Heat Rejection 13.5 kBTU/Hour
**10.8 kBTU/Hour**
17.8 kBTU/Hour
**18.3 BTU/Hour**
25. kBTU/Hour
**22.8 kBTU/Hour**
Efficiency >95.8% @ Full Load
>92.5% @ 20% Load

**>96.6% @ Full Load**
**>94.2% @ 20% Load**
>96.5% @ Full Load
>94.7% @ 20% Load

**>96.4% @ Full Load**
**>95.1% @ 20% Load**
>96.5% @ Full Load
>94.9% @ 20%

**>96.8% @ Full Load**
**>95.7% @ 20% Load**
Dimensions  27.6" x 32.8" x 80.6"
**27.6" x 32.7" x 80.7"**
35.4" x 32.8" x 80.6"
**27.6" x 32.7" x 80.7"**
35.4" x 32.8" x 80.6"
**35.4" x 32.7" x 80.7"**
Weight 855 lbs / 388 kg
**772 lbs / 350 kg**
1160 lbs / 526 kg
**860 lbs / 390kg**
1230 lbs / 558 kg
**1080 lbs / 490 kg**
Operating Temperature 0°C to 40°C
RS232 Port Included
Warranty Three years on site.  Two years on batteries.
Drawings 100 kVA 160 kVA 225 kVA
Specs G9000 Series specs
Guide Specs 100 to 225 kVA G9000 UPS Guide Specs
Enhanced Specs 100 kVA Enhanced 160 kVA Enhanced 225 kVA Enhanced
  **Enhanced represents Toshiba's latest technology, which offers higher efficiency and a lower footprint**


Specs (300 kVA to 650 kVA)

Size 300 kVA
(300 kW)
500 kVA
(500 kW)
650 kVA
(650 kW)
Model Number
T90S3S30KS6XSN
T90S3S50KS6XSN
T90S3S65KS6XSN
Input Voltage  480 V, Three-Phase, Three-Wire + Ground/Bypass Input; 480 V, Three-Phase, Three-Wire + Ground
480V, -20% to +15% (383 to 552 V without using battery)
Input Power Factor 1.0 (Unity)
Current THD < 3% at 100% Load (No input filter required)
Input Frequency 60Hz +/-10%
Output Voltage 480 V, Three-Phase, Three-Wire + Ground
Output Frequency 60Hz, +/-0.01% (In free running mode)
Output Power Factor 0.9 Lagging
Overload Capacity Inverter: 125% for 2 min; 150% for 60 sec
Bypass: 500% for one cycle
 Heat Rejection 31.7 kBTU/Hour 52.8 kBTU/Hour 68.6 kBTU/Hour
Efficiency >97% @ Full Load
>94.4% @ 20% Load
>97% @ Full Load
>94.8% @ 20% Load
>97% @ Full Load
>95.4% @ 20%
Dimensions 51.2" x 32.7" x 80.7" 70.9" x 32.7" x 80.7" 90.6" x 32.7" x 80.7"
Weight 2260 lbs / 1025 kg 3360 lbs / 1525 kg 4250 lbs / 1928 kg
Operating Temperature 0°C to 40°C
RS232 Port Included
Warranty Three years on site.  Two years on batteries.
Drawings 300 kVA 500 kVA
Specs G9000 Series specs
 Guide Specs  300 to 750 kVA G9000 UPS Guide Specs

Specs (750 kVA to 1000 kVA)

Size 750 kVA
(750 kW)
1000 kVA
(1000 kW)
Model Number
T90S3S75KS6XSN
T90S3S01MS6XSN
Input Voltage  480 V, Three-Phase, Three-Wire + Ground/Bypass Input; 480 V, Three-Phase, Three-Wire + Ground
480V, -20% to +15% (383 to 552 V without using battery)
Input Power Factor 1.0 (Unity)
Current THD < 3% at 100% Load (No input filter required)
Input Frequency 60Hz +/-10%
Output Voltage 480 V, Three-Phase, Three-Wire + Ground
Output Frequency 60Hz, +/-0.01% (In free running mode)
Output Power Factor 0.9 Lagging
Overload Capacity Inverter: 125% for 2 min; 150% for 60 sec
Bypass: 500% for one cycle
Heat Rejection 79.2 kBTU/Hour 112.8 kBTU/Hour
Efficiency >97% @ Full Load
>95.5% @ 20% Load
>96.8% @ Full Load
>95.5% @ 20% Load
Dimensions 90.6" x 32.7" x 80.7" 118.2" x 35.5" x 80.7"
Weight 4250 lbs / 1928 kg 6613 lbs / 3000 kg
Operating Temperature 0°C to 40°C
RS232 Port Included
Warranty Three years on site
Drawings 750 kVA 1000 kVA
Specs G9000 Series specs
Guide Specs 750 kVA G9000 UPS guide specs 1000 kVA G900 UPS Guide Specs

©2024 Toromont Industries. All rights reserved.